- Ken from Samlex said PST-600 can only handle blower motor startup current if it’s shorter than one second, recommended oversizing the inverter significantly for motor startup
- Dr. Bazzi said startup conditions would definitely be longer than 1 second, so we would either need a larger inverter or a motor soft starter
- Calculating battery fault current – V/R from battery to chassis under short conditions
- Overload fuse 10x rated for a period of 100-200 ms
- Relay rated for AC switching so it would have to break connection on AC side.
- Instead of AC relay, could use a power MOSFET for switching on DC side